DKG-307 User Manual V-42 (24.05.2013)
- 45 -
Coolant Level Switch Input Configuration
PGM
Parameter Definition
Unit
Fac.Set
Description
P_196
Action
0
0: Shutdown (the engine stops immediately)
1: Load Dump (the engine stops after cooldown)
2: Warning (the horn relay operates)
3: No operation
P_197
Sampling
0
0: Always
1: After holdoff timer
2: When mains present
P_198
Latching
1
0: Non latching
1: Latching
P_199
Contact type
0
0: Normally open
1: Normally closed
P_200
Switching
0
0: Battery negative
1: Battery positive
P_201
Response delay
1
0: No delay
1: Delayed (4sec)
Rectifier Fail Input Configuration
PGM
Parameter Definition
Unit
Fac.Set
Description
P_202
Action
2
0: Shutdown (the engine stops immediately)
1: Load Dump (the engine stops after cooldown)
2: Warning (the horn relay operates)
3: No operation
P_203
Sampling
2
0: Always
1: After holdoff timer
2: When mains present
P_204
Latching
1
0: Non latching
1: Latching
P_205
Contact type
0
0: Normally open
1: Normally closed
P_206
Switching
0
0: Battery negative
1: Battery positive
P_207
Response delay
0
0: No delay
1: Delayed (4sec)
Emergency Stop Input Configuration
PGM
Parameter Definition
Unit
Fac.Set
Description
P_208
Action
0
0: Shutdown (the engine stops immediately)
1: Load Dump (the engine stops after cooldown)
2: Warning (the horn relay operates)
3: No operation
P_209
Sampling
0
0: Always
1: After holdoff timer
2: When mains present
P_210
Latching
0
0: Non latching
1: Latching
P_211
Contact type
0
0: Normally open
1: Normally closed
P_212
Switching
0
0: Battery negative
1: Battery positive
P_213
Response delay
0
0: No delay
1: Delayed (4sec)