DKG-307 User Manual V-42 (24.05.2013)
- 46 -
Spare1 Input Input Configuration
PGM
Parameter Definition
Unit
Fac.Set
Description
P_214
Action
2
0: Shutdown (the engine stops immediately)
1: Load Dump (the engine stops after cooldown)
2: Warning (the horn relay operates)
3: No operation
P_215
Sampling
0
0: Always
1: After holdoff timer
2: When mains present
P_216
Latching
0
0: Non latching
1: Latching
P_217
Contact type
0
0: Normally open
1: Normally closed
P_218
Switching
0
0: Battery negative
1: Battery positive
P_219
Response delay
0
0: No delay
1: Delayed (4sec)
Spare-2 Input Input Configuration
PGM
Parameter Definition
Unit
Fac.Set
Description
P_220
Action
2
0: Shutdown (the engine stops immediately)
1: Load Dump (the engine stops after cooldown)
2: Warning (the horn relay operates)
3: No operation
P_221
Sampling
0
0: Always
1: After holdoff timer
2: When mains present
P_222
Latching
0
0: Non latching
1: Latching
P_223
Contact type
0
0: Normally open
1: Normally closed
P_224
Switching
0
0: Battery negative
1: Battery positive
P_225
Response delay
0
0: No delay
1: Delayed (4sec)